Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

SUBSCRIPTION MANAGEMENT

發(fā)行征訂

首頁(yè) >> 發(fā)行征訂 >> 征訂方式

互感器二次回路施工驗(yàn)收常見問(wèn)題分析及防范

來(lái)源:電工電氣發(fā)布時(shí)間:2024-02-01 09:01瀏覽次數(shù):219

互感器二次回路施工驗(yàn)收常見問(wèn)題分析及防范

史文玎,楊奇
(山西潞光發(fā)電有限公司,山西 長(zhǎng)治 046600)
 
    摘 要:對(duì)某火電廠施工調(diào)試期間發(fā)生電壓互感器一次設(shè)備布置差異導(dǎo)致相序相反、一次電壓與二次電壓相位相反,及電流互感器不同準(zhǔn)確級(jí)的二次繞組使用錯(cuò)誤,不同零序電流互感器對(duì)應(yīng)負(fù)荷接線錯(cuò)誤等問(wèn)題,提出了比對(duì)設(shè)備出廠圖紙與設(shè)計(jì)院圖紙差異,規(guī)范二次回路接線,設(shè)備帶電后進(jìn)行電壓與電流暫態(tài)、穩(wěn)態(tài)幅值相位檢查,對(duì)比直流電阻值及伏安特性參數(shù)等施工注意事項(xiàng)及驗(yàn)收的方法,有效確保了回路接線的正確性。
    關(guān)鍵詞: 互感器;二次繞組;布置順序;直流電阻
    中圖分類號(hào):TM45     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2024)01-0038-04
 
Analysis and Prevention of Common Problems in Construction and
Acceptance of Secondary Circuit of Mutual Inductor
 
SHI Wen-ding, YANG Qi
(Shanxi Luguang Power Generation Co., Ltd, Changzhi 046600, China)
 
    Abstract: This paper is based on the difference in the layout of the primary equipment of the voltage mutual inductor during the construction and commissioning of a thermal power plant, which leads to the opposite phase sequence, the opposite phase of the primary voltage and the secondary voltage, the wrong use of the secondary winding of the current mutual inductor with different accuracy levels, and the wrong wiring of the corresponding load of different zero-sequence current mutual inductors. The method of comparing the difference between the factory drawing and the design institute drawing, standardizating the secondary circuit wiring, checking the voltage and current transient and steady-state amplitude phase after the equipment is charged, comparing the DC resistance value and voltammeter characteristic parameters and other construction considerations and acceptance are put forward, which effectively ensures the correctness of the circuit wiring.
    Key words: mutual inductor; secondary winding; arrangement order; DC resistance
 
參考文獻(xiàn)
[1] 余云光,何磊,余煒. 電壓互感器錯(cuò)誤接線分析與防范措施探索[J] . 云南電力技術(shù),2019,47(5) :81-85.
[2] 楊奇. 一起發(fā)電機(jī)定子接地保護(hù)誤發(fā)信號(hào)的案例分析[J]. 電工電氣,2022(5) :74-76.
[3] 楊杰,徐智,鄭慶榮. 電流互感器二次回路相關(guān)故障及應(yīng)對(duì)措施探究[C]//中國(guó)水力發(fā)電工程學(xué)會(huì)自動(dòng)化專委會(huì) 2021 年年會(huì)暨全國(guó)水電廠智能化應(yīng)用學(xué)術(shù)交流會(huì)論文集,2021.
[4] 張敏,宋艷偉,曾群文. 電流互感器二次回路檢修方法探究[C]//2022 年電力行業(yè)技術(shù)監(jiān)督工作交流會(huì)暨專業(yè)技術(shù)論壇論文集,2022.
[5] 中國(guó)電力企業(yè)聯(lián)合會(huì)標(biāo)準(zhǔn)化管理中心. 繼電保護(hù)和電網(wǎng)安全自動(dòng)裝置檢驗(yàn)規(guī)程:DL/T 995—2016[S]. 北京:中國(guó)電力出版社,2018:4.