一起500 kV斷路器防跳回路異常分析及改進(jìn)

來源:電工電氣發(fā)布時(shí)間:2018-04-19 09:19 瀏覽次數(shù):714
一起500 kV斷路器防跳回路異常分析及改進(jìn)
 
顧用地,張東明,許格,劉杰,彭晨光
(國(guó)網(wǎng)浙江省電力有限公司檢修分公司,浙江 杭州 311232)
 
    摘 要:某500 kV線路斷路器出現(xiàn)多次合閘- 分閘的“跳躍”現(xiàn)象,防跳功能失敗。分析了防跳失敗的原因?yàn)閿嗦菲鞯姆珠l時(shí)間比防跳繼電器勵(lì)磁動(dòng)作時(shí)間要快,在防跳回路未形成自保持的情況下,斷路器完成了分閘,致使防跳失敗。提出兩種改進(jìn)方法,一種是把防跳繼電器更換為快速繼電器,并采用提前閉合、延后打開型的斷路器輔助接點(diǎn)作為啟動(dòng)防跳繼電器勵(lì)磁的斷路器位置接點(diǎn);另一種是在斷路器合閘控制回路中增加一條短接線,利用合閘彈簧儲(chǔ)能接點(diǎn)來實(shí)現(xiàn)防跳繼電器勵(lì)磁后的自保持,從而避免防跳失敗。
    關(guān)鍵詞:500 kV 斷路器;防跳功能;快速繼電器;儲(chǔ)能接點(diǎn)
    中圖分類號(hào):TM561     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2018)04-0032-03
 
Abnormal Analysis and Improvement of a Case of 500 kV Circuit Breaker Anti-Jumping Circuit
 
GU Yong-di, ZHANG Dong-ming, XU Ge, LIU Jie, PENG Chen-guang
(Maintenance Company, Overhaul Branch of State Grid Zhejiang Electric Power Co., Ltd, Hangzhou 311 232, China)
 
    Abstract: That certain 500 kV line circuit breaker appeared several closing-opening "jump" phenomenon causes the unsuccessful anti-jump. This paper analyzed that the reason of unsuccessful anti-jump was that the opening time of circuit breakers was shorter than the excitation action time of anti-jump relays. When the anti-jump circuit didn’t form self-holding, the circuit breaker had been opened, resulting in an anti-jump failure. Two improved methods of circuit breaker anti-jump circuits were put forward, one was to make the current anti-jump relay replaced by a fast relay, with the early closure-delayed opening of the circuit breaker auxiliary contact to start the anti-jump relay, the other was to add a short wiring in the circuit breaker closing control circuit, with the closing spring energy contacts to realize the anti-jump relay excitation self-sustaining, so as to avoid antijump failure.
    Key words: 500 kV circuit breaker; anti-jump function; fast relay; spring energy contact
 
參考文獻(xiàn)
[1] 陳慈萱. 電氣工程基礎(chǔ)[M]. 北京:中國(guó)電力出版社,2004.
[2] 龍啟峰. 一起斷路器防跳回路異常的分析與改進(jìn)[J]. 陜西電力,2015,43(5):85-87.
[3] 王建峰,裴衛(wèi)政,延謙. 防跳繼電器拒動(dòng)故障的分析[J]. 電力學(xué)報(bào),2009,24(5):416-417.
[4] 李秀卿,田嘉. 斷路器防跳接線故障分析及措施[J]. 東北電力大學(xué)學(xué)報(bào),2014,34(3):40-44.
[5] 徐春新. 防跳繼電器觸點(diǎn)卡滯導(dǎo)致斷路器反復(fù)跳躍的問題分析[J]. 電力系統(tǒng)保護(hù)與控制,2009,37(12):115-117.
[6] 周金剛,蘇展,陳開達(dá).500 kV斷路器跳躍現(xiàn)象的原因分析和思考[J]. 湖南電力,2016,36(1):63-65.