間歇性局部放電引起高壓電抗器色譜異常分析

來源:電工電氣發(fā)布時(shí)間:2018-05-09 13:09 瀏覽次數(shù):642
間歇性局部放電引起高壓電抗器色譜異常分析
 
馬飛越,伍弘
(國網(wǎng)寧夏電力有限公司電力科學(xué)研究院,寧夏 銀川 750011)
 
    摘 要:對(duì)一起750 kV高壓并聯(lián)電抗器油色譜異常缺陷進(jìn)行分析。通過長時(shí)間色譜在線監(jiān)測與離線檢測分析,判斷電抗器中缺陷為間歇性局部放電。利用多手段局部放電聯(lián)合檢測,準(zhǔn)確定位缺陷并根據(jù)其間歇性特點(diǎn)分析可能的放電原因。對(duì)該電抗器進(jìn)行吊罩檢查及實(shí)驗(yàn)室模擬試驗(yàn),驗(yàn)證了缺陷類型、位置及原因。
    關(guān)鍵詞:并聯(lián)電抗器;色譜;間歇性局放;高頻局放檢測;特高頻
    中圖分類號(hào):TM47     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2018)05-0054-05
 
Analysis on Abnormal Oil Chromatography Caused by Intermittent Partial Discharge in High Voltage Shunt Reactor
 
MA Fei-yue, WU Hong
(Power Research Institute of State Grid Ningxia Electric Power Co., Ltd, Yinchuan 750011 , China)
 
    Abstract: Analysis was made to the abnormal oil chromatography of a 750 kV high-voltage shunt reactor. By analyzing the long time online monitoring and off-line detection of the oil chromatography, it was judged that the defect in the reactor was intermittent partial discharge. Multiple methods were taken to detect the partial discharge to correctly locate the defect. According to the intermittent characteristics, this paper analyzed the possible causes of the discharge. The defect type, location and reason of the mentioned reactor were verified by the hoist checking and the laboratory simulation.
    Key words: shunt reactor; chromatography; intermittent partial discharge; high frequency partial discharge detection; ultrahigh frequency
 
參考文獻(xiàn)
[1] 姚金雄,付彬,李文輝,等. 超高壓電網(wǎng)中高壓并聯(lián)電抗器配置型式實(shí)例研究[J]. 電網(wǎng)與清潔能源,2016,32(7):65-70.
[2] 卓建宗,劉文穎,劉福潮,等. 高壓并聯(lián)電抗器對(duì)750 kV線路損耗影響機(jī)理研究[J]. 電工電能新技術(shù),2017,36(4):24-28.
[3] 宓傳龍,汪德華,李銀行,等.750 kV并聯(lián)電抗器研制[J]. 高壓電器,2009,45(3):1-4.
[4] 周宗川. 投退高壓電抗器對(duì)系統(tǒng)電壓產(chǎn)生的影響[J]. 寧夏電力,2009(4):16-19.
[5] 胡仕紅,魯?shù)欠澹踅?,? 絕緣油中溶解氣體組分含量的氣相色譜測定( 溶解平衡法) 淺析[J]. 四川電力技術(shù),2014,37(2):86-90.
[6] GB/T 17623—1998 絕緣油中溶解氣體組分含量的氣相色譜測定法[S].
[7] 孫帆,張勇,徐路強(qiáng),等. 一臺(tái)750 kV高壓電抗器局部放電故障分析[J]. 高壓電器,2015,51(3):135-139.
[8] 李小軍,李繼紅,師旭. 一起高壓電抗器色譜異常故障分析與處理[J]. 變壓器,2012,49(8):70-71.
[9] 何小劍. 一起500 kV高壓并聯(lián)電抗器乙炔含量超標(biāo)事件的原因分析及處理[J]. 機(jī)電信息,2016(15):7-8.
[10] DL/T 722—2014 變壓器油中溶解氣體分析和判斷導(dǎo)則[S].
[11] 操敦奎. 變壓器油中氣體分析診斷與故障檢查[M]. 北京:中國電力出版社,2005.
[12] 鄭書生. 變壓器繞組中局部放電特高頻定位方法研究[D]. 北京:華北電力大學(xué),2015.