Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 往年索引

一種快速解環(huán)保護(hù)及合解環(huán)方案

來源:電工電氣發(fā)布時(shí)間:2018-05-09 13:09 瀏覽次數(shù):668
一種快速解環(huán)保護(hù)及合解環(huán)方案
 
王彥國,余群兵,金震
(南京南瑞繼保電氣有限公司, 江蘇 南京 211102)
 
    摘 要:線路合環(huán)運(yùn)行時(shí),當(dāng)相鄰線路發(fā)生故障,且保護(hù)或開關(guān)拒動后,存在主變誤跳、擴(kuò)大失電范圍風(fēng)險(xiǎn)。對合環(huán)線路對繼電保護(hù)的影響進(jìn)行了分析,針對目前方案帶來的級差配合困難、設(shè)計(jì)回路改動量大、降低保護(hù)可靠性等問題提出了一種快速解環(huán)保護(hù),避免失電范圍擴(kuò)大,并對某些配網(wǎng)的合環(huán)轉(zhuǎn)電操作,提出了一種備自投方案,實(shí)現(xiàn)合解環(huán)程序化操作,在倒閘失敗后自動進(jìn)行反向合解環(huán),確保重要負(fù)荷不失電。
    關(guān)鍵詞:合環(huán)線路;解環(huán);繼電保護(hù)
    中圖分類號:TM773     文獻(xiàn)標(biāo)識碼:A     文章編號:1007-3175(2018)05-0046-05
 
A Kind of Fast Unlink Protection and Loop Closing Scheme
 
WANG Yan-guo, YU Qun-bing, JIN Zhen
(Nari-Relays Electric Co., Ltd, Nanjing 2111 02, China)
 
    Abstract: When the line operating in loop closing mode and the adjacent lines happened to break down, the protection or switch refused to work, so that there were the main transformer breaking by mistake and the power loss range-enlarged risk. This paper analyzed the loop closing line impacts on the relay protection. Aiming at the difficulty of stage difference coordination caused by the existing scheme, the greatly changed design loop and the reduced protection reliability etc problems. This paper proposed a kind of fast unlink protection to avoid the power loss range-enlarged risk. A kind of spare power automatic switching scheme was proposed for the loop closing turning electricity operation of some distribution networks to realize the operation of loop closing line routinization operation. After the back brake broke down, the reverse loop closing started atomically to ensure the important load without losing power.
    Key words: loop closing line; unlink; relay protection
 
參考文獻(xiàn)
[1] 張勇,姚建光,俞曉榮,等.具備快速合解環(huán)功能的備自投分析[J]. 江蘇電機(jī)工程,2012,31(1):61-63.
[2] 苑捷. 北京城區(qū)配電網(wǎng)合環(huán)分析[D]. 北京:華北電力大學(xué),2007.
[3] 張紅霞,閆琴,何勇毅,等. 雙回線并列運(yùn)行方式的利弊探討[J]. 寧夏電力,2009(S1):22-25.
[4] 吳玲,劉勤. 雙回線并列運(yùn)行方式探討[J]. 四川電力技術(shù),2014,37(1):59-62.
[5] 楊志棟,劉一,張建華,等. 北京10 kV配網(wǎng)合環(huán)試驗(yàn)與分析[J]. 中國電力,2006,39(3):66-69.
[6] DL/T 584—2007 3 ~ 110 kV電網(wǎng)繼電保護(hù)裝置運(yùn)行整定規(guī)程[S].
[7] GB/T 14285—2006 繼電保護(hù)和安全自動裝置技術(shù)規(guī)程[S].
[8] DL/T 684—1999 大型發(fā)電機(jī)變壓器繼電保護(hù)整定計(jì)算原則[S].
[9] 朱景富. 雙回線并列運(yùn)行方式對系統(tǒng)及保護(hù)定值的要求[J]. 繼電器,2007,35(10):64-65.