Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 文章瀏覽排名

深井接地極在變電站接地網(wǎng)中的應(yīng)用分析

來源:電工電氣發(fā)布時間:2019-01-21 13:21 瀏覽次數(shù):867
深井接地極在變電站接地網(wǎng)中的應(yīng)用分析
 
田松
(廣東電網(wǎng)有限責任公司佛山供電局,廣東 佛山 528000)
 
    摘 要:傳統(tǒng)的水平接地網(wǎng)由于面積受限難以滿足接地網(wǎng)的安全性日益提高的要求,離子接地深井這種降阻措施被逐步應(yīng)用到接地網(wǎng)的降阻中。以典型的高土壤電阻率站址220 kV變電站設(shè)計為例,結(jié)合現(xiàn)場實測和仿真計算,計算不同深井接地參數(shù)下接地網(wǎng)性能的特性參數(shù),仿真結(jié)果表明,離子接地深井降阻措施起到的效果比較有限,在變電站接地網(wǎng)設(shè)計中,不推薦使用該降阻措施。
    關(guān)鍵詞:接地網(wǎng);接地參數(shù);深井接地極;CDEGS軟件
    中圖分類號:TM645     文獻標識碼:A     文章編號:1007-3175(2019)01-0037-03
 
Application Analysis of Deep Well Grounding Electrode in Substation Grounding Grid
 
TIAN Song
(Foshan Power Supply Bureau of Guangdong Power Grid Co., Ltd, Foshan 528000, China)
 
    Abstract: The traditional horizontal grounding grid is difficult to meet the increasing safety requirements of the grounding grid due to the limited area, so that the ion-grounded deep wells are gradually applied to the resistance reduction of the grounding grid. Taking the typical design of 220 kV substation in high soil resistivity site as an example and combining with the field measurement and simulation calculation, this paper calculated the characteristic parameters of grounding grid performance under different grounding parameters of deep wells. The simulation results show that the measurement of ion-grounded deep wells resistance reduction has limited effectiveness, which is not recommended in the design of transformer substation grounding grid.
    Key words: grounding grid; grounding parameter; deep well grounding electrode; CDEGS
 
參考文獻
[1] 解廣潤. 電力系統(tǒng)接地技術(shù)[M]. 北京:中國電力出版社,1991.
[2] 何金良,曾嶸. 電力系統(tǒng)接地技術(shù)[M]. 北京:科學出版社,2007.
[3] 李謙. 電力系統(tǒng)接地網(wǎng)特性參數(shù)測量方法及其工程實踐[M]. 北京:中國電力出版社,2013.
[4] 張辰. 對離子接地極在變電站接地網(wǎng)改造中的應(yīng)用探索[J]. 計算技術(shù)與自動化,2011,30(3):62-65.
[5] 譚永浩.CDEGS軟件在變電站接地網(wǎng)安全性分析中的應(yīng)用研究[J]. 技術(shù)與市場,2011,18(10):14-17.