干式變壓器匝間短路引起的調(diào)相機(jī)跳閘故障分析
張鈺1,楊曉慧2,趙凱強(qiáng)1
(1 江蘇方天電力技術(shù)有限公司,江蘇 南京 211102;2 中國能源建設(shè)集團(tuán)江蘇省電力設(shè)計院有限公司,江蘇 南京 211102)
摘 要:介紹了一起特高壓換流站調(diào)相機(jī)勵磁系統(tǒng)的一臺小型干式變壓器匝間短路故障引起的機(jī)組跳閘事件。分析了保護(hù)動作情況及現(xiàn)場設(shè)備檢查情況,通過對故障變壓器進(jìn)行相關(guān)測試及返廠解體檢查,得出此次調(diào)相機(jī)組跳閘故障的直接原因是勵磁系統(tǒng)內(nèi)同步變壓器繞組匝間短路故障,提出了對后續(xù)投運(yùn)的調(diào)相機(jī)系統(tǒng)相關(guān)設(shè)備在出廠、調(diào)試、運(yùn)行等方面建議,為特高壓交直流系統(tǒng)旋轉(zhuǎn)設(shè)備安裝調(diào)試、驗收、運(yùn)維、檢修提供參考。
關(guān)鍵詞:變壓器;匝間短路;調(diào)相機(jī);轉(zhuǎn)子接地
中圖分類號:TM412 文獻(xiàn)標(biāo)識碼:B 文章編號:1007-3175(2019)12-0042-03
Analysis of Synchronous Condenser Tripping Fault Caused by Turn-To-Turn Short Circuit of Dry-Type Transformer
ZHANG Yu1, YANG Xiao-hui2, ZHAO Kai-qiang1
(1 Jiangsu Frontier Electric Power Technology Co., Ltd. Nanjing 2111 02, China;
2 China Energy Engineering Group Jiangsu Power Design Institute Co., Ltd, Nanjing 2111 02, China)
Abstract: Introduction was made to a synchronous condenser tripping fault caused by the turn-to-turn short circuit of a small dry-type transformer in extra-high voltage converter substation. This paper analyzed the protective action and field equipment inspection conditions. The fault transformer was carried out the relevant test and strip inspection to find that the immediate cause leading to the synchronous condenser tripping fault was the synchronous transformer winding turn-to-turn short circuit fault. This paper gave some advices of leave factory, debugging and operation etc, which provides references for the installation and debugging, acceptance inspection, operation and maintenance and overhaul of EHV AC/DC system rotating equipment.
Key words: transformer; turn-to-turn short circuit; synchronous condenser; rotor grounding
參考文獻(xiàn)
[1] 王雅婷,張一馳,周勤勇,等. 新一代大容量調(diào)相機(jī)在電網(wǎng)中的應(yīng)用研究[J]. 電網(wǎng)技術(shù),2017,41(1):22-28.
[2] 王強(qiáng),李天然,唐小波,等. 應(yīng)對多饋入直流換相失敗的同步調(diào)相機(jī)布點方法[J]. 電力系統(tǒng)自動化,2019,43(1):222-227.
[3] 崔挺,沈陽武,張斌,等.300 Mvar級同步調(diào)相機(jī)對湖南電網(wǎng)穩(wěn)定的影響研究[J]. 湖南電力,2016,36(3):1-4.
[4] 阮羚,王慶,凌在汛,等. 新型大容量調(diào)相機(jī)性能特點及工程應(yīng)用[J]. 中國電力,2017,50(12):57-61.
[5] 唐治平,彭敏放,李光明,等. 基于重復(fù)脈沖法的變壓器繞組匝間短路故障診斷[J]. 電力自動化設(shè)備,2018,38(10):153-158.
[6] 韓金華. 一起220 kV變壓器匝間短路故障分析及仿真計算[J]. 變壓器,2018,55(9):70-74.
[7] 楊可偉. 判斷變壓器繞組短路故障試驗方法的研究[J]. 變壓器,2018,55(9):44-45.
[8] 陳月營. 勵磁系統(tǒng)轉(zhuǎn)子接地故障原因分析[J]. 內(nèi)燃機(jī)與配件,2018(17):165-167.
[9] 王秀霞,王學(xué)榮,閆寒,等. 發(fā)電機(jī)轉(zhuǎn)子一點接地保護(hù)研究[J]. 華電技術(shù),2018,40(4):19-21.
[10] 劉俠,劉貞超,黃焱. 水輪發(fā)電機(jī)轉(zhuǎn)子一點接地故障分析及處理[J]. 大電機(jī)技術(shù),2017(6):40-43.