GIS斷路器殼體結(jié)構(gòu)設(shè)計仿真分析及設(shè)計改善

來源:電工電氣發(fā)布時間:2020-03-27 09:27 瀏覽次數(shù):1089
GIS斷路器殼體結(jié)構(gòu)設(shè)計仿真分析及設(shè)計改善
 
曲濤,趙維洲,董桂會,姜猛,楊魯
(青島特銳德電氣股份有限公司,山東 青島 266300)
 
    摘 要:氣體絕緣金屬封閉開關(guān)設(shè)備(GIS)的外殼一般采用鋁合金材料焊接成型,焊縫開裂相關(guān)的缺陷和故障會直接影響GIS 設(shè)備及電網(wǎng)的安全運行。以40.5 kV GIS斷路器為例,針對GIS在運輸過程中對斷路器殼體的前、后、左、右分別施加3g加速度作用工況下,進行結(jié)構(gòu)仿真分析。結(jié)果表明:斷路器殼體在考慮結(jié)構(gòu)自重和端子拉力作用下,在左向3g加速度工況下,加強筋焊縫根部存在較大應(yīng)力集中現(xiàn)象,最大值大于材料抗拉強度,結(jié)構(gòu)不安全,會導(dǎo)致殼體的破裂、漏氣。通過仿真分析,找出斷路器殼體結(jié)構(gòu)設(shè)計的薄弱點,對薄弱點有針對性的進行結(jié)構(gòu)改善,通過更合理的結(jié)構(gòu)設(shè)計,加強殼體整體的結(jié)構(gòu)強度,為GIS的可靠運行提供了保障。
    關(guān)鍵詞:GIS;斷路器殼體;ANSYS Workbench;結(jié)構(gòu)設(shè)計
    中圖分類號:TM561     文獻標識碼:A     文章編號:1007-3175(2020)03-0052-06
 
Simulation Analysis and Design Improvement of GIS Circuit Breaker Shell Structure Design
 
QU Tao, ZHAO Wei-zhou, DONG Gui-hui, JIANG Meng, YANG Lu
(Qingdao TGOOD Electric Co., Ltd, Qingdao 266300, China)
 
    Abstract: The shell of gas-insulated metal-enclosed switchgear (GIS) is generally welded with aluminum alloy. Defects and faults related to weld cracking will directly affect the safe operation of GIS equipment and the power grid.Taking the 40.5 kV GIS circuit breaker as an example, this paper introduces the finite element simulation software based on ANSYS Workbench, and 3g acceleration cased during the transportation process is applied at the front, back, left and right of the circuit breaker shell respectively . The results show that under the action of the self-weight and terminal tension of the circuit breaker casing, there is a large stress concentration at the root of the rib weld in the left 3g acceleration condition. The maximum value is greater than the tensile strength of the material and the structure is not safe. It can cause cracking and air leakage of the casing. Through simulation analysis, the weak points of the circuit breaker shell structure design are found, the structural improvement of the weak points is targeted, and the structural strength of the whole shell is strengthened through a more reasonable structural design, which provides a reliable operation for the combined electrical equipment. The guarantee also shows the importance of structural design simulation analysis during the shell design process.
    Key words: GIS; circuit breaker shell; ANSYS Workbench; structural design
 
參考文獻
[1] 張欣,李高揚,黃榮輝,等. 不同運行年限的GIS缺陷率統(tǒng)計分析與運維建議[J]. 高壓電器,2016,52(3):184-188.
[2] 郭清海,鄺石. GIS設(shè)備滲漏原因分析及對策[J].電網(wǎng)技術(shù),2000,24(9):8-9.
[3] 張麗娟,張?zhí)旌?,趙航. GIS設(shè)備漏氣故障常見原因分析及防范措施[J]. 山東電力技術(shù),2018,45(1):71-74.
[4] 龔源,彭鵬,周家戌,等.110 kV GIS母線裂紋故障實例分析[J]. 電工技術(shù),2018(3):77-78.
[5] 徐國政,張節(jié)容,錢家驪,等. 高壓斷路器原理和應(yīng)用[M]. 北京:清華大學(xué)出版社,2000.
[6] 洪國耀,趙羲英,陳冰. 小型化SF6氣體絕緣金屬封閉開關(guān)設(shè)備的研究開發(fā)[J]. 高壓電器,2012,48(10):78-82.
[7] 中國電器工業(yè)協(xié)會. 充氣高壓開關(guān)設(shè)備用鋁合金外殼:GB/T 28819—2012[S]. 北京:中國標準出版社,2012:10-12.
[8] 黎斌.SF6 高壓電器設(shè)計[M]. 北京:機械工業(yè)出版社,2015.
[9] 國家電網(wǎng)公司. 國家電網(wǎng)公司十八項電網(wǎng)重大反事故措施[M]. 北京:中國電力出版社,2007.
[10] 侯月玲,李育文,王寧,等. 基于ANSYS的GIS殼體應(yīng)力分析研究[J]. 煤礦機械,2009,30(4):53-55.
[11] 張建周,楊俊朋,李剛. GIS鋁制筒體表面變形質(zhì)量問題分析[J]. 電工電氣,2013(9):55-56.
[12] 周萬盛,姚君山. 鋁及鋁合金的焊接[M]. 北京:機械工業(yè)出版社,2006.
[13] 劉建軍,張建國,陳大兵. GIS焊接技術(shù)及焊接接頭失效案例分析[J]. 電工電氣,2014(11):42-44.