核級充電器輸出振蕩故障分析及處理
賈后康1,楊亞炬2
(1 國核示范電站有限責任公司,山東 威海 264300;2 上海核工程研究設(shè)計院有限公司,上海 200235)
摘 要:以AP1000核電機組依托項目調(diào)試過程中,1E級充電器對放電完成后的蓄電池進行再充電過程中出現(xiàn)的輸出波動及主熔絲熔斷故障為例,對故障原因進行了分析,并提出采取更新主控板固件及標準接口板等相應(yīng)的處理措施,經(jīng)仿真模擬及現(xiàn)場驗證,AP1000 1E級充電器輸出振蕩及主熔絲熔斷故障得到了有效處理,保障了1E 級直流及UPS 系統(tǒng)的安全穩(wěn)定運行。
關(guān)鍵詞:AP1000核電機組;1E級充電器;輸出振蕩;主熔絲熔斷;回路控制器
中圖分類號:TM623 文獻標識碼:B 文章編號:1007-3175(2020)06-0043-04
Analysis and Solution of Battery Charger Output Oscillation Incident
JIA Hou-kang1, YANG Ya-ju2
(1 State Nuclear Power Demonstration Plant Co.,Ltd, Weihai 264300, China;
2 Shanghai Nuclear Engineering Research & Design Institute Co.,Ltd, Shanghai 200235, China)
Abstract: Taking the AP1000 nuclear power unit's debugging process based on the project as an example, the output fluctuations and main fuse blowing faults occurred during the recharging of the battery after the discharge was completed by the 1E-Class charger. The corresponding processing measures such as the control board firmware and standard interface board, after simulation and field verification, the output oscillation of the AP1000 1E-Class charger and the main fuse blowing fault have been effectively handled, ensuring the safe and stable operation of the 1E DC and UPS systems.
Key words: AP1000 nuclear power unit; 1E-Class charger; output oscillation; main fuse blowing; loop controller
參考文獻
[1] 林誠格. 非能動安全先進壓水堆核電技術(shù)[M]. 北京:原子能出版社,2010.
[2] 高海翔. 大功率鉛酸蓄電池快速脈沖充電控制器設(shè)計[D]. 南京:東南大學,2009.
[3] 林知明,魏九妹,劉珺. 滯環(huán)PID控制在蓄電池充電器應(yīng)用中的研究[J]. 華東交通大學學報,2014,31(5):93-98.
[4] 李喬,吳捷. 自抗擾控制及其在DC-DC變換器中的應(yīng)用[J]. 電工技術(shù)學報,2005,20(1):83-88.