控制回路感應(yīng)電壓分析與對(duì)策

來源:電工電氣發(fā)布時(shí)間:2020-07-15 15:15 瀏覽次數(shù):874
控制回路感應(yīng)電壓分析與對(duì)策
 
沈建位1,謝名勇2
(1 寧波職業(yè)技術(shù)學(xué)院,浙江 寧波 315800;2 浙江聯(lián)能電氣有限公司,浙江 衢州 324000)
 
    摘 要:針對(duì)某電廠輸煤電機(jī)控制回路在調(diào)試過程發(fā)生的問題,對(duì)故障情況進(jìn)行了分析;為減少交流長(zhǎng)距離控制回路感應(yīng)電壓的影響,提出了改變繼電器參數(shù)、減少感應(yīng)電壓和寄生電容的產(chǎn)生等處理對(duì)策,并結(jié)合現(xiàn)場(chǎng)情況,采用電感補(bǔ)償?shù)姆椒?,有效抑制了感?yīng)電壓對(duì)控制回路的影響。
    關(guān)鍵詞:控制回路;感應(yīng)電壓;分布電容
    中圖分類號(hào):TM645.2+1     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號(hào):1007-3175(2020)07-0047-04
 
Analysis and Countermeasure of Induced Voltage in Control Circuit
 
SHEN Jian-wei1, XIE Ming-yong2
(1 Ningbo Polytechnic, Ningbo 315800, China; 2 Zhejiang Union Power Electric Co., Ltd, Quzhou 324000, China)
 
    Abstract: This paper analyzed the problems that occurred during the commissioning process of a coal-fired motor control loop of a power plant, the failure conditions. In order to reduce the influence of the induced voltage of the AC long-distance control loop, the countermeasures such as changing the relay parameters, reducing the induced voltage and the generation of parasitic capacitance are proposed; and combined with the on-site situation, the method of inductance compensation is used to effectively suppress the influence of the induced voltage on the control loop.
    Key words: control circuit; induced voltage; distributed capacitance
 
參考文獻(xiàn)
[1] 欒瑞瑛. 控制回路中電纜感應(yīng)電壓分析及解決方案[J]. 通訊世界,2017(21):237-239.
[2] 林樹國(guó). 控制電纜感應(yīng)電壓引起機(jī)泵頻繁故障停機(jī)事故[J]. 電工技術(shù),2016(1):65-66.
[3] 韓吉成,趙樹燾,李紅星,陳雨. 由分布電容引起的控制故障及其處理[J]. 電世界,2017,58(2):47-48.