換流站交流濾波場高端光CT異常態(tài)故障診斷
王嘉毅,吳繼順,俞林廣,劉葉杰
(浙江省送變電工程有限公司,浙江 杭州 310016)
摘 要:±800 kV 換流站隨著運行時限的逐漸增長,交流濾波器場小組開關(guān)高端光CT故障率也越來越高。針對±800 kV 換流站交流濾波器場運行過程中光CT出現(xiàn)的異常態(tài),結(jié)合現(xiàn)場歷史數(shù)據(jù)對光回路進(jìn)行了分析,并結(jié)合2020 年某換流站年度檢修工作,對交流濾波器高端光CT進(jìn)行故障診斷和排查。通過光時域分析儀等檢修方法,逐級檢查出光回路故障點,實現(xiàn)了對換流站交流濾波器5631B相高端光CT和5634A相高端光CT故障的消除。
關(guān)鍵詞:換流站;高端光CT;故障診斷
中圖分類號:TM452 文獻(xiàn)標(biāo)識碼:A 文章編號:1007-3175(2021)01-0054-06
Fault Diagnosis of Abnormal High-End Optical CT
in ACFilter Field of Converter Station
WANG Jia-yi, WU Ji-shun, YU Lin-guang, LIU Ye-jie
(Zhejiang Power Transmission and Transformation Engineering Co., Ltd, Hangzhou 310016, China)
Abstract: With the gradual increase of the operating time limit of the ±800 kV converter station, the failure rate of the high-end opticalCT of the AC filter field group switch is getting higher and higher. In this paper aim at the abnormal state of the optical CT during the operationof the AC filter field of the ±800 kV converter station, the optical circuit is analyzed based on the historical data of the site, and combinedwith the annual maintenance work of a converter station in 2020, the high-end optical CT perform fault diagnosis and troubleshooting.Through maintenance methods such as optical time domain analyzer, the fault points of the optical circuit are checked step by step, and thefaults of the 5631 B-phase high-end optical CT and 5634 A-phase high-end optical CT of the converter station AC filter are eliminated.
Key words: converter station; high-end optical CT; fault diagnosis
參考文獻(xiàn)
[1] 舒印彪,劉澤洪,高理迎,等.±800 kV 6400 MW特高壓直流輸電工程設(shè)計[J] . 電網(wǎng)技術(shù),2006,30(1):1-8.
[2] 彭舟,康文,張宏,等. 鵝城換流站光CT運行情況分析及改進(jìn)措施[J]. 電力學(xué)報,2016,31(1):41-46.