Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 往年索引

一起500 kV變壓器油中乙炔超標原因分析與處理

來源:電工電氣發(fā)布時間:2022-04-20 12:20 瀏覽次數(shù):408

一起500 kV變壓器油中乙炔超標原因分析與處理

孫海軍
(大唐國際發(fā)電股份有限公司浙江分公司,浙江 杭州 310016)
 
    摘 要:及時有效地診斷變壓器在運行過程中潛在的內(nèi)部缺陷, 對保障電力系統(tǒng)安全穩(wěn)定運行具有重要意義。針對某電廠 500 kV 變壓器油中乙炔含量超標情況,持續(xù)跟蹤乙炔含量變化趨勢,通過變壓器油色譜測量數(shù)據(jù)三比值法計算,判斷故障類型為低能量放電。退出變壓器運行并返廠維修,經(jīng)過變壓器解體吊芯檢查發(fā)現(xiàn)放電故障點,經(jīng)放電故障原因分析,并針對性維修,最終消除放電故障。
    關鍵詞:變壓器;有載分接開關;色譜分析;乙炔;低能量放電
    中圖分類號:TM411     文獻標識碼:B     文章編號:1007-3175(2022)04-0045-04
 
Cause Analysis and Treatment of Excessive Acetylene in
500 kV Transformer Oil
 
SUN Hai-jun
(Datang International Power Generation Co., Ltd. Zhejiang Branch, Hangzhou 310016, China)
 
    Abstract: To diagnose potential internal defects of transformers during operation timely and effectively is vital to ensure the safe and stable operation of the power system. In a power plant, the acetylene content in the 500 kV transformer oil exceeded the standard. This paper tracked the changing trend of acetylene content and determined that the fault type is low-energy discharge through the three-ratio method of transformer oil chromatographic measurement data. The power plan withdrew the transformer from the operation and returned it to the factory for maintenance. It found the discharge fault point after the suspended core examination. After analysis, this research conducts selective maintenance to eliminate the discharge failure.
    Key words: transformer; on-load switch; chromatographic analysis; acetylene; low-energy discharge
 
參考文獻
[1] 葉技. 油色譜分析在變壓器故障診斷中的應用研究[J]. 中國電業(yè)(技術版),2012(7) :27-29.
[2] 施家煒,劉璨. 變壓器油色譜數(shù)據(jù)異常的原因分析及處理研究[J]. 中國設備工程,2020(20) :78-79.
[3] 張亞平,胡曉玲,祁炯. 一起由油中乙炔含量變化判斷變壓器內(nèi)部故障的典型案例[J] . 湖北電力,2010(z1) :119-120.
[4] 電力行業(yè)電力變壓器標準化技術委員會. 變壓器油中溶解氣體分析和判斷導則:DL/T 722—2014[S] .北京:中國電力出版社,2015 :1-19.
[5] 趙燕玲. 變壓器故障油色譜分析方法[J] . 科技傳播,2012(21) :107-108.
[6] 馮易. 電力變壓器的維護及故障診斷分析[J] . 電子世界,2014(10) :503-504.