Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 文章瀏覽排名

溫度對配電一二次融合成套設(shè)備測量準(zhǔn)確度影響

來源:電工電氣發(fā)布時間:2023-03-04 10:04 瀏覽次數(shù):408

溫度對配電一二次融合成套設(shè)備測量準(zhǔn)確度影響

趙海洋,滕達,姜曉君,侯永濤
(中訊郵電咨詢設(shè)計院有限公司,北京 100048)
 
    摘要:配電網(wǎng)一二次設(shè)備融合后,二次設(shè)備因長期處于一次高溫環(huán)境中,其內(nèi)部電子器件性能易受溫度影響。分析了溫度對二次設(shè)備內(nèi)元件及信號調(diào)理電路的影響,基于高低溫試驗環(huán)境箱搭建了試驗測試平臺,通過采集二次設(shè)備互感器的比值差和相位差進行測量精準(zhǔn)度的對比分析,為提高測量精準(zhǔn)度,提出采用非線性軟件補償方式,并進行了軟件算法原理分析和試驗驗證。試驗結(jié)果表明,取樣電阻和差分運算放大電路的溫度相關(guān)系數(shù)是影響二次設(shè)備采集準(zhǔn)確度的關(guān)鍵,溫度變化會造成二次設(shè)備的測量準(zhǔn)確度下降,在高溫60 ℃、低溫-30 ℃左右已不能滿足配電開關(guān)的要求,加入非線性軟件補償后比值差變化在0.15%~0.3% 之間波動,可以有效提高測量準(zhǔn)確度。
    關(guān)鍵詞: 配電網(wǎng);溫度變化;一二次融合;測量準(zhǔn)確度;二次設(shè)備
    中圖分類號:TM642     文獻標(biāo)識碼:B     文章編號:1007-3175(2023)02-0057-06
 
Temperature Effect on Measuring Accuracy of Primary and
Secondary Fusion Equipment of Distribution Network
 
ZHAO Hai-yang, TENG Da, JIANG Xiao-jun, HOU Yong-tao
(China Information Technology Designing & Consulting Institute Co., Ltd, Beijing 100048, China)
 
    Abstract: The performance of internal electronic devices of the secondary equipment is susceptible to temperature because the secondary equipment has been in the primary high temperature environment for a long time after primary and secondary fusion of the distribution network. The paper analyzes temperature effects on internal devices of the secondary equipment and signal conditioning circuit, and it also establishes a test platform based on the high and low temperature environmental chamber. The measuring accuracy is compared and analyzed by collecting ratio error and phase difference of the secondary equipment transducers. Moreover, the paper puts forward a nonlinear software compensation method and conducts the software algorithm principle analysis and test verification to increase the measuring accuracy. The results show that the temperature correlation coefficient of sampling resistance and differential operational amplifier circuit are the key factors to acquisition accuracy of the secondary equipment. Temperature variation decreases measuring accuracy of the secondary equipment. It cannot meet the requirement of distribution switches at high temperature of 60 ℃ and low temperature of -30 ℃. The measuring accuracy can be effectively increased by employing the nonlinear software compensation method which ensures the fluctuation of the ratio error between 0.15% and 0.3%.
    Key words: distribution network; temperature variation; primary and secondary fusion; measuring accuracy; secondary equipment
 
參考文獻
[1] 李于達,王海燕,劉剛,等. 配電網(wǎng)中的饋電自動化技術(shù)發(fā)展綜述[J] . 電網(wǎng)技術(shù),2006,30(S1):242-245.
[2] 張敏,崔琪,吳斌. 智能配電網(wǎng)饋線自動化發(fā)展及展望[J]. 電網(wǎng)與清潔能源,2010,26(4):41-43.
[3] 李紅青,張志丹,朱吉然,等. 配電網(wǎng)新型一二次融合成套設(shè)備測試方法研究[J] . 湖南電力,2018,38(2):47-52.
[4] 胡良蓉,駱虎,魏泉,等. 一種智能開關(guān)設(shè)備的集成及試驗研究[J] . 高壓電器,2015,51(4):62-66.
[5] 賈曉明,戴建卓,賈勇勇,等. 低壓綜合配電箱溫升影響因素研究[J]. 電工電氣,2021(5):37-40.
[6] 陳金汕. 成套開關(guān)設(shè)備中使用小型斷路器存在問題的分析[J]. 電工電氣,2014(5):63-64.
[7] 周雄兵. 溫度試驗對電子元器件的性能影響分析[J]. 信息通信,2016(11):257-258.
[8] 萬雄,張貴新,王強,等. 影響中壓電子式互感器準(zhǔn)確度問題的研究[J] . 高壓電器,2009,45(3):61-65.
[9] 王炳瑞,蔡雪峰,張文霞. 環(huán)境溫度對互感器誤差的影響分析[J]. 內(nèi)蒙古石油化工,2013,39(11):88-89.
[10] 潘志新,劉利國,錢程,等. 一種新型便攜式多功能局部放電在線檢測儀器的設(shè)計[J] . 電工電氣,2019(5):41-48.
[11] 胡浩亮, 李前, 盧樹峰, 等. 電子式互感器誤差的兩種校驗方法對比[J] . 高電壓技術(shù),2011,37(12):3022-3027.
[12] 張冶,蔡穎凱,回茜,等. 一二次融合的智能集成開關(guān)應(yīng)用的研究與分析[J] . 電氣工程學(xué)報,2022,17(1):199-205.
[13] 胡冉,吳夕發(fā). 配電開關(guān)一二次融合的影響因素分析[J]. 中國設(shè)備工程,2022(5):184-185.
[14] 張瑞卿,蔣義然,禹江,等. 溫度補償技術(shù)在配電一二次融合 FTU 中的應(yīng)用[J] . 信息記錄材料,2021,22(11):158-160.
[15] 江東,單薏,劉緒坤,等. 函數(shù)擬合法力數(shù)字傳感器的非線性和溫度補償[J] . 傳感器與微系統(tǒng),2016,35(2):16-19.
[16] 錢政,梅志剛,羅承沐. 電子式互感器中數(shù)據(jù)采集系統(tǒng)的實現(xiàn)與誤差補償[J] . 高壓電器,2004,40(1):37-39.