一起超高壓變電站低抗絕緣油檢測異常缺陷分析

來源:電工電氣發(fā)布時(shí)間:2023-03-04 10:04 瀏覽次數(shù):316

一起超高壓變電站低抗絕緣油檢測異常缺陷分析

王從剛,錢苗旺,郁飛
(國網(wǎng)江蘇省電力有限公司連云港供電分公司,江蘇 連云港 222000)
 
    摘 要:針對一起在超高壓變電站油浸式低壓并聯(lián)電抗器 (低抗) 絕緣油檢測中發(fā)現(xiàn)總烴超標(biāo)的事故,通過對絕緣油溶解氣體含量分析,借助三比值法初步推斷低抗內(nèi)部存在中溫過熱故障,進(jìn)行包含直流電阻、絕緣電阻、阻抗、介損及電容量等項(xiàng)目的診斷性試驗(yàn),分析低抗缺陷原因,并對低抗進(jìn)行解體驗(yàn)證。結(jié)果表明,低抗缺陷的原因?yàn)榻拥仄林写嬖阢~箔片異常搭接,進(jìn)而引起環(huán)流引發(fā)局部過熱,造成異常搭接處被灼燒,導(dǎo)致總烴超標(biāo)。
    關(guān)鍵詞: 變電站;油浸式低壓并聯(lián)電抗器;總烴;過熱故障;缺陷分析
    中圖分類號:TM472 ;TM855     文獻(xiàn)標(biāo)識碼:B     文章編號:1007-3175(2023)02-0047-04
 
Analysis on Abnormal Detection of Low-Voltage Parallel Reactor
Insulating Oil of a Ultra-High Voltage Substation
 
WANG Cong-gang, QIAN Miao-wang, YU Fei
(Lianyungang Power Supply Branch, State Grid Jiangsu Electric Power Co., Ltd, Lianyungang 222000, China)
 
    Abstract: An accident which the total hydrocarbon from insulating oil of the oil-immersed low-voltage parallel reactor of a ultra-high voltage substation exceeded standard happened, so the paper analyzes the dissolved gas content of insulating oil, and it is preliminarily inferred through three-ratio method that medium temperature overheat fault exists inside of the low-voltage parallel reactor. Then, diagnostic tests are conducted on DC resistance, insulation resistance, impedance, medium loss, and capacitance to analyze why the low-voltage parallel reactor has defects, and disassembling the low-voltage parallel reactor verifies the correctness of this analysis. According to the results, the reason for defects of the low-voltage parallel reactor is that copper foils in the earthing panel are connected abnormally. As a consequence, circulating current contributes to local overheating and the abnormal connection burns, causing the total hydrocarbon exceeding standard.
    Key words: substation; oil-immersed low-voltage parallel reactor; total hydrocarbon; overheat fault; defect analysis
 
參考文獻(xiàn)
[1] 徐鵬,甘強(qiáng),譚婷月. 一起 35 kV 油浸式并聯(lián)電抗器故障分析[J] . 電力電容器與無功補(bǔ)償,2021,42(6):76-80.
[2] 孫毅, 李然, 張祥虎, 等. 一起 1 000 kV 特高壓并聯(lián)電抗器氫氣含量異常分析[J] . 電工電氣,2021(12):65-67.
[3] 蘇光,周星,李云偉,等. 變電站低壓并聯(lián)電抗器選型研究[J]. 華北電力技術(shù),2012(2):66-68.
[4] 徐康健,陳桂增. 變壓器安裝后油中出現(xiàn)乙炔的案例分析[J]. 電工電氣,2011(6):63-64.
[5] 王馳宇, 方圓, 秦天, 等. 開斷并聯(lián)電抗器過電壓機(jī)理分析及應(yīng)對措施[J] . 湖北電力,2021,45(3):60-66.
[6] 田肖飛,孫文星,楊賢,等. 油浸式并聯(lián)鐵心電抗器缺陷分析及整改措施[J] . 廣東電力,2019,32(2):144-151.
[7] 樊陽文,季斌,張科乾,等.500 kV 官山變電站油浸式電抗器故障分析及處理措施[J] . 電力學(xué)報(bào),2018,33(4):322-325.
[8] 劉旸,韓洪剛,隋新,等. 一起油浸式電抗器火災(zāi)事故分析與防火對策研究[J] . 變壓器,2020,57(9):85-87.