±800 kV特高壓直流線(xiàn)路地線(xiàn)斷線(xiàn)故障分析

來(lái)源:電工電氣發(fā)布時(shí)間:2023-03-04 10:04 瀏覽次數(shù):344

±800 kV特高壓直流線(xiàn)路地線(xiàn)斷線(xiàn)故障分析

魏小龍1,張璐2,閆可為3,李新民2,韓彥華2,李偉2,孔志戰(zhàn)1
(1 國(guó)網(wǎng)陜西省電力有限公司,陜西 西安 710048;
2 國(guó)網(wǎng)陜西省電力有限公司電力科學(xué)研究院,陜西 西安 710100;
3 國(guó)網(wǎng)陜西省電力有限公司超高壓公司,陜西 西安 710075)
 
    摘 要:提升抗冰能力對(duì)線(xiàn)路安全運(yùn)行至關(guān)重要。對(duì)某 ±800 kV 特高壓直流線(xiàn)路地線(xiàn)斷線(xiàn)故障現(xiàn)場(chǎng)的環(huán)境及錄波進(jìn)行了分析,開(kāi)展了地線(xiàn)斷口靜態(tài)分析及掃描電鏡試驗(yàn)、拉斷力試驗(yàn),并對(duì)導(dǎo)地線(xiàn)間距進(jìn)行了仿真計(jì)算。試驗(yàn)和仿真計(jì)算表明:特高壓直流導(dǎo)地線(xiàn)覆冰厚度差異較大,隨著地線(xiàn)覆冰厚度的增加,導(dǎo)地線(xiàn)間間距逐漸減小,在大風(fēng)作用下極易發(fā)生空氣間隙不足放電。本次特高壓線(xiàn)路故障原因?yàn)橹馗脖?/span>引起導(dǎo)地線(xiàn)空氣間隙距離不足,導(dǎo)致放電燒傷和拉斷地線(xiàn)。微地形區(qū)線(xiàn)路覆冰情況可能超過(guò)設(shè)計(jì)值,應(yīng)考慮現(xiàn)場(chǎng)實(shí)際覆冰厚度、導(dǎo)地線(xiàn)覆冰厚度差值、故障區(qū)段微氣象和微地形等因素,確保線(xiàn)路設(shè)計(jì)運(yùn)行有充足裕度。
    關(guān)鍵詞: ±800 kV 特高壓直流線(xiàn)路;地線(xiàn);覆冰;斷線(xiàn);故障分析
    中圖分類(lèi)號(hào):TM723     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2023)02-0041-06
 
Analysis of Ground Wire Disconnection Fault of ± 800 kV
Ultra-High Voltage DC Line
 
WEI Xiao-long1, ZHANG Lu2, YAN Ke-wei3, LI Xin-min2, HAN Yan-hua2, LI Wei2, KONG Zhi-zhan1
(1 State Grid Shaanxi Electric Power Co., Ltd, Xi’an 710048, China;
2 Electric Power Research Institute of State Grid Shaanxi Electric Power Co., Ltd, Xi’an 710100, China;
3 Ultra High Voltage Company of State Grid Shaanxi Electric Power Co., Ltd, Xi’an 710075, China)
 
    Abstract: To improve the anti-icing ability is vital for safe operation of the line. The paper analyzes the environment and waveform record of the ground wire disconnection fault field of ±800 kV ultra-high voltage(UHV) DC line, makes static analysis of the ground wire fracture,conducts scanning electron microscope and breaking force test, and carries out the simulation calculation of guide wire spacing. According to the test and simulation calculation, there is a big difference of the ground wire icing thickness of UHV DC. When the ground wire icing thickness increases, the spacing between conductors and ground wires gradually decreases which is likely to contribute to discharge because of insufficient air gap under the strong wind. The reason for this UHV line fault is that the insufficient air gap of ground wires caused by icing contributes to discharge to burn and break ground wires. The line icing of micro-terrain region is possible to exceed the design value, so factors such as the actual on-site icing thickness, ground wire icing thickness differential value, micro-meteorology and micro-topography of fault section should be taken into consideration to ensure operation of the line.
    Key words: ±800 kV ultra-high voltage DC line; ground wire; icing; disconnection; fault analysis
 
參考文獻(xiàn)
[1] 黃新波. 輸電線(xiàn)路覆冰關(guān)鍵影響因素分析[J] . 高電壓技術(shù),2011,37(7):1677-1682.
[2] 陳立軍,吳謙,石美,等. 輸電線(xiàn)路覆冰檢測(cè)技術(shù)發(fā)展綜述[J] . 化工自動(dòng)化及儀表,2011,38(2):129-133.
[3] 李嘉祥,李宏男,付興. 輸電線(xiàn)路覆冰脫落參數(shù)影響研究[J]. 電力建設(shè),2016,37(4):76-83.
[4] 周超,曹陽(yáng),李林. 輸電線(xiàn)路覆冰問(wèn)題綜述[J] .電力建設(shè),2013,34(9):37-41.
[5] 劉昌盛,劉和志,姜丁尤,等. 輸電線(xiàn)路覆冰舞動(dòng)研究綜述[J] . 科學(xué)技術(shù)與工程,2014,14(24):156-164.
[6] 黃斌,徐姍姍,蘇文宇. 輸電線(xiàn)路覆冰研究綜述[J].電瓷避雷器,2012(1):27-32.
[7] 尹暉,王晶晶. 輸電線(xiàn)路覆冰與微氣象參數(shù)和覆冰時(shí)間的研究[J] . 高壓電器,2017,53(12):145-150.
[8] 朱曄,王海濤,吳念,等. 輸電線(xiàn)路覆冰在線(xiàn)監(jiān)測(cè)動(dòng)態(tài)預(yù)警模型[J] . 高電壓技術(shù),2014,40(5):1374-1381.
[9] 曹永興,張昌華,黃琦,等. 輸電線(xiàn)路覆冰在線(xiàn)監(jiān)測(cè)及預(yù)警技術(shù)的國(guó)內(nèi)外研究現(xiàn)狀[J] . 華東電力,2011,39(1):96-99.
[10] 王黎明,李海東,梅紅偉,等. 輸電線(xiàn)路覆冰在線(xiàn)監(jiān)測(cè)系統(tǒng)國(guó)內(nèi)外研究綜述[J] . 高壓電器,2013,49(6):48-56.
[11] 巢亞鋒,岳一石,王成,等. 輸電線(xiàn)路融冰、除冰技術(shù)研究綜述[J] . 高壓電器,2016,52(11):1-9.
[12] 李新民,朱寬軍,李軍輝. 輸電線(xiàn)路舞動(dòng)分析及防治方法研究進(jìn)展[J] . 高電壓技術(shù),2011,37(2):484-490.
[13] 張弦. 輸電線(xiàn)路中微地形和微氣象的覆冰機(jī)制及相應(yīng)措施[J]. 電網(wǎng)技術(shù),2007,31(S2):87-89.
[14] 黃新波,徐冠華,肖淵,等. 塔線(xiàn)體系脫冰不平衡張力影響因素分析[J]. 中國(guó)電力,2017,50(11):96-102.
[15] 侯鐳,王黎明,朱普軒,等. 特高壓線(xiàn)路覆冰脫落跳躍的動(dòng)力計(jì)算[J] . 中國(guó)電機(jī)工程學(xué)報(bào),2008,28(6):1-6.
[16] 郝艷捧,魏發(fā)生,王斌,等. 特殊地形下輸電線(xiàn)路等值覆冰厚度計(jì)算模型有效性分析和改進(jìn)研究[J].電網(wǎng)技術(shù),2022,46(7):2786-2793.
[17] 康基偉. 微地形和小氣候區(qū)線(xiàn)路覆冰影響因素分析及工程實(shí)例[J] . 鄭州大學(xué)學(xué)報(bào)(工學(xué)版),2013,34(1):103-107.
[18] 謝景海,袁敬中,郭嘉,等. 一種輸電線(xiàn)路多參數(shù)可視化物聯(lián)監(jiān)測(cè)系統(tǒng)[J] . 科學(xué)技術(shù)與工程,2021,21(12):4975-4981.