交流控制回路感應(yīng)電壓計(jì)算分析與故障處理
李學(xué)龍,劉德龍,桂松
(雅礱江流域水電開(kāi)發(fā)有限公司,四川 成都 610051)
摘 要:交流控制回路間存在感應(yīng)電壓,嚴(yán)重情況下感應(yīng)電壓會(huì)影響被控元件的可靠動(dòng)作,影響設(shè)備正常運(yùn)行。分析了交流控制回路感應(yīng)電壓產(chǎn)生的原因,結(jié)合某水電站地下廠房加壓送風(fēng)風(fēng)機(jī)控制回路中接觸器無(wú)法釋放的問(wèn)題,提出消除感應(yīng)電壓的三種方法,并進(jìn)行計(jì)算分析,通過(guò)并聯(lián)電容的方法解決現(xiàn)場(chǎng)問(wèn)題,該故障處理方法可行有效。
關(guān)鍵詞: 感應(yīng)電壓;接觸器;RLC 電路;故障處理
中圖分類號(hào):TM572 文獻(xiàn)標(biāo)識(shí)碼:B 文章編號(hào):1007-3175(2023)05-0036-04
Analysis and Troubleshooting of Induced Voltage in AC Control Circuit
LI Xue-long, LIU De-long, GUI-Song
(Yalong River Hydropower Development Co., Ltd, Chengdu 610051, China)
Abstract: The induced voltage exists in AC control circuits, and it may affect the reliable actions of controlled components to disturb the normal operation of equipments in some serious cases. First, the paper analyzes the causes of induced voltage in AC control circuits. Then, it takes the release problem of a contactor in the control circuits occurring to the pressurization fan in the underground powerhouse of a hydropower station as the research object, and proposes three methods to eliminate the induced voltage. After calculation and analysis, the paper chooses the method of parallel capacitors to solve the release problem, which verifies this troubleshooting method feasible and effective.
Key words: induced voltage; contactor; RLC circuit; troubleshooting
參考文獻(xiàn)
[1] 吉蘭. 長(zhǎng)距離交流控制電纜電容電流電氣故障分析及處理[J]. 新世紀(jì)水泥導(dǎo)報(bào),2016,22(5):72-74.
[2] 蘇秀蘋(píng),田海波,付哲,等. 交流接觸器動(dòng)作值仿真計(jì)算[J]. 機(jī)械設(shè)計(jì)與制造,2020(12):19-23.
[3] 田海波. 交流接觸器電磁系統(tǒng)結(jié)構(gòu)分析及穩(wěn)健性研究[D]. 天津:河北工業(yè)大學(xué),2019.
[4] 陳錚錚,歐陽(yáng)本紅,胡凱,等. 交直流電纜混合敷設(shè)的電磁感應(yīng)[J] . 高電壓技術(shù),2018,44( z1):146-150.
[5] 張宓,張憲發(fā),都優(yōu). 控制電纜產(chǎn)生分布電容的分析及處理[J] . 石油化工自動(dòng)化,2017,53(5):67-69.
[6] 曹輝. 遠(yuǎn)程控制的交流接觸器抗干擾措施應(yīng)用[J].機(jī)電信息,2019(33) :46-47.
[7] 欒瑞瑛. 控制回路中電纜感應(yīng)電壓分析及解決方案[J]. 通訊世界,2017(21):237-238.