35 kV單母線分段變電站母線故障的保護(hù)分析與改進(jìn)

來源:電工電氣發(fā)布時(shí)間:2023-07-27 13:27 瀏覽次數(shù):250

35 kV單母線分段變電站母線故障的保護(hù)分析與改進(jìn)

陳錫磊,葉漢錚,徐文琴
(國網(wǎng)浙江慈溪市供電有限公司,浙江 慈溪 315300)
 
    摘 要:針對一起 35 kV 單母線分段變電站 35 kV 母線故障時(shí)導(dǎo)致的全站停電事故,分析了事故中各繼電保護(hù)和備自投裝置的動(dòng)作情況,明確了變電站全停的原因。分析結(jié)果顯示,在目前的繼電保護(hù)配置方式下,35 kV 母線故障時(shí)只能由線路對側(cè)變電站的線路保護(hù)動(dòng)作切除故障,本站母線設(shè)備將遭受多次短路電流的沖擊,并最終導(dǎo)致全站停電。根據(jù)單母線分段母線故障的特點(diǎn),提出了 3 種不同的繼電保護(hù)改進(jìn)方案,能夠最大程度地避免全站停電,提高終端變電站的供電可靠性。
    關(guān)鍵詞: 單母線分段;母線故障;全站停電;改進(jìn)方案
    中圖分類號:TM77     文獻(xiàn)標(biāo)識(shí)碼:B     文章編號:1007-3175(2023)07-0033-04
 
Analysis and Improvement for the Bus Failure Protection of 35 kV
Sectionalized Single-Bus Substation
 
CHEN Xi-lei, YE Han-zheng, XU Wen-qin
(State Grid Zhejiang Cixi Power Supply Co., Ltd, Cixi 315300, China)
 
    Abstract: The paper analyzes the action behaviors of relay protection and backup power automatic switch and nails down causes of this blackout based on a 35 kV sectionalized single-bus substation power outage accident caused by the 35 kV bus failure. The analysis shows that the present relay protection configure scheme can cut off failures through the opposite side substation when the 35 kV bus fault happens,while the short-circuit current can surge bus equipments several times, leading to the final substation power outage accident. Three relay protection improved schemes are proposed according to the characteristics of bus failures of sectionalized single-bus. They can avoid substation power outage to the greatest extent and increase the power supply reliability of terminal substations.
    Key words: sectionalized single-bus; bus failure; substation power outage; improved scheme
 
參考文獻(xiàn)
[1] 張豐,郭碧媛. 備自投裝置在單母分段接線中應(yīng)用存在的問題及解決措施[J] . 電力系統(tǒng)保護(hù)與控制,2011,39(7):133-135.
[2] 周超,王洪富,李洪成,等. 一起主變死區(qū)故障導(dǎo)致 110 kV 變電站全站失電事故分析[J]. 電力學(xué)報(bào),2015,30(2):143-148.
[3] 王利平,程浪,胡楊. 電流互感器位置與死區(qū)故障保護(hù)動(dòng)作行為分析[J] . 四川電力技術(shù),2022,45(1):40-44.
[4] 中國電力企業(yè)聯(lián)合會(huì).3 kV~110 kV 電網(wǎng)繼電保護(hù)裝置運(yùn)行整定規(guī)程:DL/T 584—2017[S]. 北京:中國電力出版社,2018:1-5.
[5] 中國電力企業(yè)聯(lián)合會(huì). 電力系統(tǒng)繼電保護(hù)設(shè)計(jì)技術(shù)規(guī)范:DL/T 5506—2015[S]. 北京:中國計(jì)劃出版社,2015:1-4.