Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 文章瀏覽排名

自然積污絕緣子串等值鹽密簡化測量方法的有效性

來源:電工電氣發(fā)布時(shí)間:2016-03-25 08:25 瀏覽次數(shù):749

自然積污絕緣子串等值鹽密簡化測量方法的有效性 

馬杏可1,王少華2,朱亦振3 
1 嘉興電力局,浙江 嘉興 314033;2 浙江省電力公司電力科學(xué)研究院,浙江 杭州 310014;
3 金華電業(yè)局,浙江 金華 321017
 
 

摘 要: 以輸電線路掛網(wǎng)運(yùn)行的110 kV 及220 kV 自然積污懸式絕緣子串為研究對象,基于每片絕緣子的等值附鹽密度(ESDD) 測試結(jié)果,對自然積污絕緣子串污穢度的簡化測量方法進(jìn)行了研究,分析了不同測量方法的污穢度測試結(jié)果差異。結(jié)果表明:對于110 kV 絕緣子串,取上、下各1 片,上、中、下各1 片,上、下各2 片絕緣子ESDD 均值作為整串絕緣子ESDD 均值,其差異不大,偏差約為5%。對于220 kV 絕緣子串,取上、中、下各1 片絕緣子ESDD 均值作為整串絕緣子ESDD 均值,偏差較大;為準(zhǔn)確表征220 kV 絕緣子串的污穢度,建議取上、中、下各3 片或每隔1 片取1 片絕緣子ESDD 的均值。
關(guān)鍵詞: 自然積污;絕緣子串;污穢度;等值附鹽密度
中圖分類號:TM216 文獻(xiàn)標(biāo)識碼:B 文章編號:1007-3175(2013)09-0052-03


Effectiveness of Simplified Measuring Method of Equivalent Salt Deposit Density of Naturally Polluted Insulator String 

MA Xing-ke1, WANG Shao-hua2, ZHU Yi-zhen3 
1 Jiaxing Electric Power Bureau, Jiaxing 314033, China; 2 Zhejiang Electric Power Company Electric Power Research Institute, Hangzhou 310014, China; 3 Jinhua Electric Power Bureau, Jinhua 321017, China 
 

Abstract: Taking 11 0 kV and 220 kV naturally polluted suspension insulator strings on transmission lines as study objects and based on measured results of each piece of naturally polluted insulator for the equivalent salt deposit density (ESDD), this paper studied the simplified measuring method of pollution level of naturally polluted insulator strings. Analysis was made on differences of tested result of pollution level between different measuring methods. The results show that as for 11 0 kV insulator strings, there is nearly no obvious difference among the average ESDD value of the upper one and below one piece of insulator, the average ESDD value of the upper one, middle one and below one piece of insulator, and the average ESDD value of the upper two and below two pieces of insulators. The error between the real value and the simplified measuring value is less than 5%; as for 220 kV insulator strings, the error between the average ESDD value of the upper one, middle one and below one piece of insulator is obvious. In order to accurately evaluate the pollution level of 220 kV insulator strings, it is recommended that the upper three, middle three and below three pieces of insulators or one in every two pieces of insulators should be sampled.
             Key words: natural pollution; insulator string;pollution level; equivalent salt deposit density


參考文獻(xiàn)
[1] 王少華,方玉群,胡旭光,等.自然積污絕緣子等值鹽密的累積規(guī)律[J].絕緣材料,2011,44(4):52-54.
[2] 應(yīng)偉國,胡旭光.500 kV運(yùn)行線路絕緣子飽和鹽密實(shí)測結(jié)果分析[J].中國電力,2004,37(6):29-32.
[3] 胡錫棟,董皆.浙西地區(qū)輸電線路絕緣子串自然積污特性[J].電工電氣,2012(9):25-28.
[4] GB/T 16434-1996 高壓架空線路和發(fā)電廠、變電所環(huán)境污區(qū)分級及外絕緣選擇標(biāo)準(zhǔn)[S].
[5] Q/GDW 152-2006 電力系統(tǒng)污區(qū)分級與外絕緣選擇標(biāo)準(zhǔn)[S].