Suzhou Electric Appliance Research Institute
期刊號: CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 文章瀏覽排名

主變近區(qū)短路后的電氣試驗分析與診斷

來源:電工電氣發(fā)布時間:2016-04-05 16:05 瀏覽次數(shù):767

主變近區(qū)短路后的電氣試驗分析與診斷 

劉愛華 
廣東電網(wǎng)公司江門供電局,廣東 江門 529000 
 

摘 要:220 kV 變電站10 kV 出線電流互感器CT 突然發(fā)生三相短路,主變受到短路電流沖擊,停運后通過常規(guī)試驗絕緣電阻、直流電阻及氣體色譜分析,并結(jié)合繞組變形頻響分析方法進行綜合分析,準(zhǔn)確地判斷了變壓器低壓繞組B 相存在輕微變形的故障性質(zhì),為變壓器是否重新投入運行或及時退出運行提供了重要參考。
關(guān)鍵詞:變壓器;絕緣電阻;直流電阻;色譜分析;繞組變形
中圖分類號:TM406 文獻(xiàn)標(biāo)識碼:B 文章編號:1007-3175(2013)11-0050-03


Analysis and Diagnosis of Main Transformer near Zone Electrical Short Circuit Test 

LIU Ai-hua 
Jiangmen Power Supply Bureau of Guangdong Grid Coporation, Jiangmen 529000, China 
 

Abstract: Three-phase short circuit suddenly happened in 10 kV outlet line current transformer (CT) of 220 kV substation. The shortcircuit current had impacts on the main transformer, so the main transformer stopped operation to be carried out test inspection. Analysis was made to routine experiments of insulation resistance, direct current resistance and gas chromatographic. Combined with the analysis method of winding deformation frequency response, this paper analyzed various data to correctly judge the faults property at B-phase of the main transformer, which could be used to guide whether the transformer should come on the line or not.
        Key words: transformer; insulation resistance; direct current resistance; chromatographic analysis; winding deformation


參考文獻(xiàn)
[1] Q/CSG 114002-2011 電力設(shè)備預(yù)防性試驗規(guī)程[S].
[2] 何平,文習(xí)山.變壓器繞組變形的頻率響應(yīng)分析法綜述[J].高電壓技術(shù),2006,32(5):37-40.
[3] 劉利成,季克超,黃曙霞.變壓器出口短路的危害及預(yù)防措施[J].變壓器,2006,43(2):24-25.