諧振接地系統(tǒng)暫態(tài)選線啟動(dòng)條件研究

來源:電工電氣發(fā)布時(shí)間:2016-04-06 12:06 瀏覽次數(shù):24

諧振接地系統(tǒng)暫態(tài)選線啟動(dòng)條件研究 

曾振松,王鵬 
國網(wǎng)福建省電力有限公司三明供電公司,福建 三明 365000 
 

摘 要:介紹了HHT時(shí)頻分析法并將其應(yīng)用于系統(tǒng)母線暫態(tài)故障特征量的提取,提出了一種采用HHT時(shí)頻分析法的諧振接地系統(tǒng)暫態(tài)選線啟動(dòng)判據(jù)。采用MATLAB的SPS工具箱搭建仿真模型,通過對系統(tǒng)在四種典型及多種不同接地故障條件下的仿真分析,驗(yàn)證了所提算法的準(zhǔn)確性優(yōu)于傳統(tǒng)判據(jù)。
關(guān)鍵詞:諧振接地系統(tǒng);暫態(tài)選線啟動(dòng)條件;HHT時(shí)頻分析法
中圖分類號:TM711 文獻(xiàn)標(biāo)識碼:A 文章編號:1007-3175(2014)08-0038-05


Research on Start Condition for Transient Line Selection in Resonant Earthed System 

ZENG Zhen-song, WANG Peng 
Sanming Power Company, Fujian Electric Power Co., Ltd of State Grid, Sanming 365000, China 
 

Abstract: Introduction was made to the HHT time frequency analysis method and the method was applied in extraction of transient fault signature values of system bus. This paper proposed a kind of resonant earthed system’s start criterion for transient line selection adopting the HHT time frequency analysis method. The simulation model was built up by the SPS toolbox in Matlab. The simulation analysis of resonant earthed system in four special and several different fault conditions verifies that the accuracy of the proposed algorithm is superior to that of the traditional criterion.
             Key words: resonant earthed system; start condition for transient line selection; HHT time frequency analysis method


[1] 康忠健,李丹丹,劉曉林.應(yīng)用非工頻暫態(tài)分量的配電網(wǎng)故障選線方法[J].電力自動(dòng)化設(shè)備,2011,31(4):1-6.
[2] 張保會(huì),趙慧梅,張文豪,等.基于特征頻帶內(nèi)暫態(tài)零序電流特點(diǎn)的配電網(wǎng)單相接地故障選線方法[J].電力系統(tǒng)保護(hù)與控制,2008,36(13):5-10.
[3] 束洪春,彭仕欣,李斌,等.利用測后模擬的諧振接地系統(tǒng)故障選線方法[J].中國電機(jī)工程學(xué)報(bào),2008,28(16):59-63.
[4] 肖白,穆鋼,黎平,等.配電網(wǎng)單相接地故障選線方案[J].繼電器,2005,33(24):1-5.
[5] 束洪春,趙文淵,彭仕欣.配電網(wǎng)纜-線混合線路故障選線的HHT檢測方法[J].電力自動(dòng)化設(shè)備,2009,29(5):4-9.
[6] 李天云,趙妍,季小慧,等.HHT方法在電力系統(tǒng)故障信號分析中的應(yīng)用[J].電工技術(shù)學(xué)報(bào),2005,20(6):87-91.
[7] 陳可,李野,陳瀾.EEMD分解在電力系統(tǒng)故障信號檢測中的應(yīng)用[J].計(jì)算機(jī)仿真,2010,27(3):263-266.
[8] 張楊,劉志剛.EEMD在電能質(zhì)量擾動(dòng)檢測中的應(yīng)用[J].電力自動(dòng)化設(shè)備,2011,31(12):86-91.
[9] 董文智,張超.基于EEMD能量熵和支持向量機(jī)的軸承故障診斷[J].機(jī)械設(shè)計(jì)與研究,2011,27(5):53-56.