等溫松弛電流法在XLPE電纜老化狀態(tài)評(píng)估中的應(yīng)用

來源:電工電氣發(fā)布時(shí)間:2016-04-06 13:06 瀏覽次數(shù):21

等溫松弛電流法在XLPE電纜老化狀態(tài)評(píng)估中的應(yīng)用 

林敏1,張子陽1,李淑琦2,吳建東2,尹毅2 
(1 江蘇省電力公司,江蘇 南京 210024;
2 上海交通大學(xué) 電氣工程系,上海 200240)
 
 

摘 要: 設(shè)計(jì)了一種新型的等溫松弛電流測試系統(tǒng),測試電路中考慮到微電流測試的抗干擾問題,基于該套系統(tǒng)分別研究了未老化、人工加速老化和實(shí)際運(yùn)行的XLPE 絕緣電纜的等溫松弛電流,研究表明采用等溫松弛電流法不僅能夠有效評(píng)估實(shí)驗(yàn)室電纜的老化程度,同時(shí)能夠有效評(píng)估現(xiàn)場運(yùn)行電纜。
關(guān)鍵詞: 等溫松弛電流法;絕緣電纜;極化;退極化;電纜老化
中圖分類號(hào):TM247+.1 文獻(xiàn)標(biāo)識(shí)碼:A 文章編號(hào):1007-3175(2014)09-0046-04


Application of Constant Temperature Relaxation Current Method in XLPE Insulated Power Cable Ageing State Evaluation 

LIN Min1, ZHANG Zi-yang1, LI Shu-qi2, WU Jian-dong2, YIN Yi2 
(1 Jiangsu Electric Power Company, Nanjing 210024, China;
2 Department of Electrical Engineering, Shanghai Jiaotong University, Shanghai 200240, China)
 
 

Abstract: This paper designed a new type of constant temperature relaxation current test system, which considered the anti-interference problem of micro-current test in the testing circuit. On the basis of this system, this paper studied the non-ageing, manual speedup ageing and constant temperature relaxation current of actually running cross linked polyethylene (XLPE) insulated power cable. Research shows that adopting the constant temperature relaxation current method could not only evaluate the ageing degree of cable in lab effectively, but also evaluate the site running cable.
        Key words: constant temperature relaxation current method; insulated power cable; polarization; depolarization; cable ageing


參考文獻(xiàn)
[1] Birkner P. Field experience with a conditionbased maintenance program of 20-kV XLPE distribution system using IRC-analysis[J].IEEE Transactions on Power Delivery, 2004,19(1):3-8.
[2] 李明華,董明,嚴(yán)璋.一種新的絕緣測試方法——回復(fù)電壓法[J].高電壓技術(shù),2002,28(8):43-45.
[3] Oyegoke Bolarin, Hyvonen Petri, Aro Mattti,Gao Ning. Application of Dielectric Response Measurement on Power Cable Systems[J].IEEE Transactions on Dielectrics and Electrical Insulation, 2003, 10(5):862-873.
[4] Oyegoke B S. Improved condition assessment of XLPE insulated cables using the isothermal relaxation current technique[C]//2006 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2006:477-480.
[5] 王雅群,尹毅,李旭光,等. 溫松弛電流用于10 kV XLPE 電纜壽命評(píng)估方法的研究[J]. 電工技術(shù)學(xué)報(bào),2009,24(9):33-37.
[6] Chen Jiqun Wang Shoutai.Method of Estimating the Remaining Life of the 10kV XLPE Cable Operated 10 Years[C]//The 6th International Conference on Properties and Applications of Dielectric Materials, Xi'an China, 2000, 1:204-208.
[7] Oyegoke B S, Foottit F, Birtwhistle D, Lyall J, et al. Condition Assessment of XLPE Insulated Cables Using Isothermal Relaxation Current Technique[C]//IEEE Power Engineering Society General Meeting, 2006:18-22.
[8] Kranz H G, Steinbrink D F M. IRC-Analysis: A new test procedure for laid XLPE-Cables[C]//10th International Symposium on High Voltage Engineering, Montreal, 1997:207-210.
[9] Beigert M, Kranz H G. Destruction Free Ageing Diagnosis of Power Cable Insulation Using the Isothermal Relaxation Current Analysis[C]//Conference Record of the 1994 IEEE International Symposium on Electrical Insulation, Pittsburgh,
Pennsylvania, 1994:17-21.