Suzhou Electric Appliance Research Institute
期刊號(hào): CN32-1800/TM| ISSN1007-3175

Article retrieval

文章檢索

首頁 >> 文章檢索 >> 文章瀏覽排名

直流分量時(shí)間常數(shù)對(duì)斷路器非對(duì)稱開斷性能影響分析

來源:電工電氣發(fā)布時(shí)間:2016-08-18 10:18 瀏覽次數(shù):9
直流分量時(shí)間常數(shù)對(duì)斷路器非對(duì)稱開斷性能影響分析
 
劉小浩,劉旭,李健,蘇其莉,劉超峰,王磊
(河南平高電氣股份有限公司,河南 平頂山 467001)
 
    摘 要:從短路電流的有效值、燃弧時(shí)差、電弧能量等方面分析了直流分量時(shí)間常數(shù)對(duì)斷路器非對(duì)稱電流開斷性能的影響,給出了非對(duì)稱短路計(jì)算模型及計(jì)算方法。結(jié)果表明直流分量時(shí)間常數(shù)越大,短路電流中直流分量越大且衰減越慢,燃弧時(shí)差越大,電弧能量越大,電流過零時(shí)di /dt 降低,TRV 參數(shù)亦有所降低,且非對(duì)稱電流開斷時(shí),直流分量時(shí)間常數(shù)增大將導(dǎo)致斷路器的開斷條件變得苛刻。
    關(guān)鍵詞:直流分量時(shí)間常數(shù);非對(duì)稱開斷;短路電流有效值;燃弧時(shí)差
    中圖分類號(hào):TM561     文獻(xiàn)標(biāo)識(shí)碼:A     文章編號(hào):1007-3175(2016)08-0047-04
 
Analysis of Direct Current Component Time Constant Influence on
Asymmetrical Breaking Ability of Circuit Breakers
 
LIU Xiao-hao, LIU Xu, LI Jian, SU Qi-li, LIU Chao-feng, WANG Lei
(Henan Pinggao Electric Co., Ltd., Pingdingshan 467001, China)
 
    Abstract: This paper analyzed the direct current (DC) component time constant influence on asymmetrical current breaking ability of circuit breakers from the aspects of effective value of short-circuit current, difference of arcing time, arc energy and so on, and gave the calculation model and method of asymmetrical short-circuit. The results show that the bigger the DC component time constant is, the bigger the DC component in short-circuit current is, the slower the attenuation is, the bigger the difference of arcing time is , the bigger the arc energy is. When the current is zero, the parameters of di/dt and TRV are decreased. When the asymmetrical current cuts off, the increase of the DC component time constant will make the breaking conditions of circuit breakers more rigorous.
    Key words: direct current component time constant; asymmetrical breaking; effective value of short-circuit current; difference of arcing time
 
參考文獻(xiàn)
[1] 林莘. 現(xiàn)代高壓電器技術(shù)[M]. 北京:機(jī)械工業(yè)出版社,2011.
[2] GB 1984—2014 高壓交流斷路器[S].
[3] 吳盛剛,孔祥軍,李向陽,等. 非對(duì)稱電流開斷合成試驗(yàn)方法分析[J]. 電工電氣,2011(10):49-53.
[4] 李剛,姚斯立,杜煒,等.UHV 斷路器非對(duì)稱電流開斷試驗(yàn)方法研究[J]. 高壓電器,2013,49(4):20-24.
[5] IEC 62271-308:2002 高壓開關(guān)設(shè)備和控制設(shè)備 第308 部分:非對(duì)稱短路試驗(yàn)方式T100a 的導(dǎo)則[S].