一起高壓電抗器繞組溫度異常的處理及臨時監(jiān)視方法

來源:電工電氣發(fā)布時間:2017-04-21 09:21 瀏覽次數(shù):8
一起高壓電抗器繞組溫度異常的處理及臨時監(jiān)視方法
 
李顯鵬,劉杰,顧用地,程興民
(國網(wǎng)浙江省電力公司檢修分公司,浙江 杭州 311232)
 
    摘 要:變壓器繞組溫度因表計卡澀或附加溫升回路異常時常造成溫度誤差過大、TA 開路等,使得現(xiàn)場和監(jiān)控系統(tǒng)無法對繞組溫度進行有效監(jiān)視。提出一種高壓電抗器繞組溫度的臨時監(jiān)視方法,在現(xiàn)場油溫表計上標注高壓電抗器附加溫升,將附加溫升作為繞組溫度表計的基礎讀數(shù),實現(xiàn)繞組溫度就地監(jiān)視;同時監(jiān)控系統(tǒng)的繞組溫度由油溫與廠家提供的附加溫升或高壓側電流軟件模擬附加溫升取得,無需停電,即可實現(xiàn)高壓電抗器繞組溫度的就地和遠方監(jiān)視,實際案例驗證了該方法的有效性。
    關鍵詞:高壓電抗器;繞溫;附加溫升;臨時監(jiān)視方法
    中圖分類號:TM47      文獻標識碼:B      文章編號:1007-3175(2017)04-0043-03
 
Disposal and Temporary Monitoring Method for a Case of Abnormal Temperature in High-Voltage Reactor Winding
 
LI Xian-peng, LIU Jie, GU Yong-di, CHENG Xing-min
(Overhaul Branch of State Grid Zhejiang Electric Power Company, Hangzhou 311 232, China)
 
Abstract: Because of the metering jam or abnormal circuit of additional temperature rise, the transformer winding temperature will have big errors with open circuit to make the scene and the monitoring system unable to carry out effective monitoring for the winding temperature. This paper raised a kind of temporary monitoring method for high-voltage reactor winding temperature, labeling additional temperature rise of high-voltage reactor on site oil temperature meter. The additional temperature rise was acted as the basic reading of winding temperature metering, so as to realize the winding temperature monitoring locally, meanwhile the winding temperature of the monitoring system was provided by oil temperature or additional temperature rise of the vender, as well as the current software simulated additional temperature rise at high-voltage side, without outage, the system could realize locally and remotely monitoring the high-voltage reactor winding temperature. The practical case verifies the validity of this method.
Key words: high-voltage reactor pressure; winding temperature; additional temperature rise; temporary monitoring method
 
參考文獻
[1] JB/T 8450—2005 變壓器用繞組溫控器[S].
[2] 俞立凡,李慧蓉. 變壓器繞組溫度計異常的原因及改進建議[J]. 變壓器,2007,44(11):51-56.
[3] 孫勝濤,石巖,鄒旭. 變壓器溫度數(shù)據(jù)異常分析及處理措施[J]. 變壓器,2008,45(5):62-63.
[4] 吉瑞,雍麗華. 變壓器遠方測溫系統(tǒng)測量誤差的產生原因和應對措施[J]. 電力安全技術,2012,14(2):61-62.
[5] 劉瀾波,余美海,袁恒,等. 變壓器溫度遙測誤差探討[J]. 貴州電力技術,2010,13(4):25-28.
[6] 孫亞洲,王延瑞. 淺析變壓器油溫數(shù)據(jù)的異常與溫度計座的關系[J]. 變壓器,2010,47(8):55-56.
[7] 楊潔民,王振. 換流變繞組溫度測量裝置故障原因分析及測量裝置原理介紹[J]. 變壓器,2014,51(8):48-51.