一起GIS設(shè)備漏氣及現(xiàn)場交流耐壓試驗擊穿故障分析

來源:電工電氣發(fā)布時間:2017-08-23 12:23 瀏覽次數(shù):7
一起GIS設(shè)備漏氣及現(xiàn)場交流耐壓試驗擊穿故障分析
 
胡全義,秘立鵬,劉天奇,張欣偉
(國網(wǎng)內(nèi)蒙古東部電力有限公司電力科學(xué)研究院,內(nèi)蒙古 呼和浩特 010020)
 
    摘 要:針對某220 kV 變電站66 kV 氣體絕緣金屬封閉組合電器(GIS) 因盆式絕緣子出現(xiàn)裂痕發(fā)生漏氣事件,介紹了設(shè)備漏氣故障點發(fā)現(xiàn)過程,解體處理后進(jìn)行主回路絕緣試驗過程中出現(xiàn)擊穿現(xiàn)象,通過閃絡(luò)定位儀準(zhǔn)確定位到擊穿氣室,再次解體發(fā)現(xiàn)導(dǎo)電座上有明顯的磕碰痕跡,改變了導(dǎo)電座周圍的空間電場分布,導(dǎo)致在耐壓過程中導(dǎo)電座下側(cè)局部電場發(fā)生畸變,耐壓過程中最終在絕緣子表面發(fā)生了沿面閃絡(luò)放電。試驗驗證了閃絡(luò)定位儀在閃絡(luò)故障檢測及故障點定位應(yīng)用中的準(zhǔn)確性和有效性,可在高壓設(shè)備交接試驗中推廣。
    關(guān)鍵詞:GIS;盆式絕緣子;SF6 氣體泄漏;交流耐壓;定位
    中圖分類號:TM595     文獻(xiàn)標(biāo)識碼:B      文章編號:1007-3175(2017)08-0043-04
 
A Case of Insulated Swithgear Equipment Air Leakage and Site AC Withstand Voltage Test Breakdown Fault Analysis
 
HU Quan-yi, MI Li-peng, LIU Tian-qi, ZHANG Xin-wei
(State Grid East Inner Mongolia Electric Power Company Research Institute, Hohhot 010020, China)
 
    Abstract: In allusion to the leakage event of basin-type insulator cracks in the 66 kV gas insulated switchgear (GIS) in the 220 kV substation, introduction was made to the discovery process of equipment air leakage fault points and the punchthrough in the process of major loop insulation test after disintegration disposal. The flashover position indicator was used to carry out accurate positioning to the breakdown air chamber. There were obvious signs of bumps on the conductive seat, which changed the space electric field around the conductive seats and caused electric field distortion in the process of withstand voltage downside the conductive seat. In the process of withstand voltage the flashover discharged along surface of the insulators finally. The test verifies the accuracy and validity of the flashover position indicator applied in the flashover faults testing and positioning.
    Key words: gas insulated switchgear; basin-type insulator; SF6 leakage; AC withstand voltage; positioning
 
參考文獻(xiàn)
[1] 姜敏,楊衛(wèi)東,喬朝霞. 氣體絕緣組合電器局部放電分析[J]. 山西電力,2011(4):28-29.
[2] 李秀衛(wèi),王慶玉,毛惠卿,等. 一起組合電器內(nèi)部絕緣故障綜合分析[J]. 高壓電器,2012,48(8):99-102.
[3] 黃純德,田赟,冀晉川.220 kV 變電站組合電器盆式絕緣子開裂分析[J]. 山西電力,2013(4):26-28.
[4] 陳昱同,郭建宏,劉楊,等.220 kV某GIS盆式絕緣子漏氣原因分析及處理措施[J]. 高壓電器,2015,51(12):196-200.
[5] 趙畹君. 高壓直流輸電工程技術(shù)[M]. 北京:中國電力出版社,2011.
[6] 沈宏強,葛占雨. GIS交流耐壓試驗及其對發(fā)現(xiàn)內(nèi)部異常情況的作用[J]. 安裝,2013(S1):62-64.
[7] 崔巨勇,楊鶴,韋德福,等. GIS現(xiàn)場閃絡(luò)故障定位關(guān)鍵技術(shù)應(yīng)用[J]. 東北電力技術(shù),2016,37(8):59-62.
[8] 高立超,孫興彬,楊志華,等.330 kV GIS設(shè)備現(xiàn)場交流耐壓試驗擊穿故障分析[J]. 電氣技術(shù),2016,17(8):86-88.
[9] 曲文韜,黃銳,呂俊濤.220 kV GIS設(shè)備漏氣原因分析及預(yù)防措施[J]. 電力科學(xué)與工程,2013,29(8):21-26.
[10] 劉旭.220 kV GIS設(shè)備交流耐壓擊穿故障簡析[J].安徽電力,2012,29(3):5-7.